How to organize multiple electrical wires going into an ultra thin recessed light?





.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty{ margin-bottom:0;
}






up vote
3
down vote

favorite












I am installing ultra thin recessed light in the basement and it comes with a very small metal box (probably 2x4 in in size). Due to the old wiring of the house, there are 5 wires coming in totally: power to light 1, power to light 2, 2 switches, and the light itself. It's going to be very "crowded" because the wire nut will have to fit like 4-5 wires.



I would like to "connect" everything" outside of the ultra thin metal box and only leave 3 wires (white, black, ground) coming into the box itself.



I am thinking of a few options:




  1. Use an electrical box and connect everything in there but leave 3 wires out to go into the recessed box. Then close the box with a lid and just sort of "throw" it up in the ceiling somewhere (no screw or mount into joists).


  2. Tear up the ceiling to find a joist and install a Round Hard-Shell Ceiling Box then connect everything there. However, the hard part is to connect existing wiring since some are not long enough. I may have to create additional lumber support. Either that or I have to use the ceiling box that has a metal bar to mount both joists. Regardless, this is major ceiling work and drywall fixes.



I am leaning toward Option 1 as I doubt there is any unforeseen issue. What are your thoughts?



Reference: the light I bought is



enter image description here



https://www.amazon.com/gp/product/B079GLKCV7/ref=oh_aui_detailpage_o05_s00?ie=UTF8&psc=1










share|improve this question




























    up vote
    3
    down vote

    favorite












    I am installing ultra thin recessed light in the basement and it comes with a very small metal box (probably 2x4 in in size). Due to the old wiring of the house, there are 5 wires coming in totally: power to light 1, power to light 2, 2 switches, and the light itself. It's going to be very "crowded" because the wire nut will have to fit like 4-5 wires.



    I would like to "connect" everything" outside of the ultra thin metal box and only leave 3 wires (white, black, ground) coming into the box itself.



    I am thinking of a few options:




    1. Use an electrical box and connect everything in there but leave 3 wires out to go into the recessed box. Then close the box with a lid and just sort of "throw" it up in the ceiling somewhere (no screw or mount into joists).


    2. Tear up the ceiling to find a joist and install a Round Hard-Shell Ceiling Box then connect everything there. However, the hard part is to connect existing wiring since some are not long enough. I may have to create additional lumber support. Either that or I have to use the ceiling box that has a metal bar to mount both joists. Regardless, this is major ceiling work and drywall fixes.



    I am leaning toward Option 1 as I doubt there is any unforeseen issue. What are your thoughts?



    Reference: the light I bought is



    enter image description here



    https://www.amazon.com/gp/product/B079GLKCV7/ref=oh_aui_detailpage_o05_s00?ie=UTF8&psc=1










    share|improve this question
























      up vote
      3
      down vote

      favorite









      up vote
      3
      down vote

      favorite











      I am installing ultra thin recessed light in the basement and it comes with a very small metal box (probably 2x4 in in size). Due to the old wiring of the house, there are 5 wires coming in totally: power to light 1, power to light 2, 2 switches, and the light itself. It's going to be very "crowded" because the wire nut will have to fit like 4-5 wires.



      I would like to "connect" everything" outside of the ultra thin metal box and only leave 3 wires (white, black, ground) coming into the box itself.



      I am thinking of a few options:




      1. Use an electrical box and connect everything in there but leave 3 wires out to go into the recessed box. Then close the box with a lid and just sort of "throw" it up in the ceiling somewhere (no screw or mount into joists).


      2. Tear up the ceiling to find a joist and install a Round Hard-Shell Ceiling Box then connect everything there. However, the hard part is to connect existing wiring since some are not long enough. I may have to create additional lumber support. Either that or I have to use the ceiling box that has a metal bar to mount both joists. Regardless, this is major ceiling work and drywall fixes.



      I am leaning toward Option 1 as I doubt there is any unforeseen issue. What are your thoughts?



      Reference: the light I bought is



      enter image description here



      https://www.amazon.com/gp/product/B079GLKCV7/ref=oh_aui_detailpage_o05_s00?ie=UTF8&psc=1










      share|improve this question













      I am installing ultra thin recessed light in the basement and it comes with a very small metal box (probably 2x4 in in size). Due to the old wiring of the house, there are 5 wires coming in totally: power to light 1, power to light 2, 2 switches, and the light itself. It's going to be very "crowded" because the wire nut will have to fit like 4-5 wires.



      I would like to "connect" everything" outside of the ultra thin metal box and only leave 3 wires (white, black, ground) coming into the box itself.



      I am thinking of a few options:




      1. Use an electrical box and connect everything in there but leave 3 wires out to go into the recessed box. Then close the box with a lid and just sort of "throw" it up in the ceiling somewhere (no screw or mount into joists).


      2. Tear up the ceiling to find a joist and install a Round Hard-Shell Ceiling Box then connect everything there. However, the hard part is to connect existing wiring since some are not long enough. I may have to create additional lumber support. Either that or I have to use the ceiling box that has a metal bar to mount both joists. Regardless, this is major ceiling work and drywall fixes.



      I am leaning toward Option 1 as I doubt there is any unforeseen issue. What are your thoughts?



      Reference: the light I bought is



      enter image description here



      https://www.amazon.com/gp/product/B079GLKCV7/ref=oh_aui_detailpage_o05_s00?ie=UTF8&psc=1







      electrical wiring recessed-lighting junction-box






      share|improve this question













      share|improve this question











      share|improve this question




      share|improve this question










      asked Nov 19 at 8:28









      HP.

      54921432




      54921432






















          1 Answer
          1






          active

          oldest

          votes

















          up vote
          4
          down vote



          accepted










          Use an old work box to house the splices



          There's a simple way out of this, and that's to use an old work box mounted into the ceiling drywall to house the electrical splices. A 3 gang switch box will do the trick, or you can use a 4 11/16" square box that's 1.5" or deeper if you can get an old work mountable version of that. (Really, anything that supplies more than 29.5 in3 of space will do.)






          share|improve this answer





















            Your Answer








            StackExchange.ready(function() {
            var channelOptions = {
            tags: "".split(" "),
            id: "73"
            };
            initTagRenderer("".split(" "), "".split(" "), channelOptions);

            StackExchange.using("externalEditor", function() {
            // Have to fire editor after snippets, if snippets enabled
            if (StackExchange.settings.snippets.snippetsEnabled) {
            StackExchange.using("snippets", function() {
            createEditor();
            });
            }
            else {
            createEditor();
            }
            });

            function createEditor() {
            StackExchange.prepareEditor({
            heartbeatType: 'answer',
            convertImagesToLinks: false,
            noModals: true,
            showLowRepImageUploadWarning: true,
            reputationToPostImages: null,
            bindNavPrevention: true,
            postfix: "",
            imageUploader: {
            brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
            contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
            allowUrls: true
            },
            noCode: true, onDemand: true,
            discardSelector: ".discard-answer"
            ,immediatelyShowMarkdownHelp:true
            });


            }
            });














            draft saved

            draft discarded


















            StackExchange.ready(
            function () {
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f150905%2fhow-to-organize-multiple-electrical-wires-going-into-an-ultra-thin-recessed-ligh%23new-answer', 'question_page');
            }
            );

            Post as a guest















            Required, but never shown

























            1 Answer
            1






            active

            oldest

            votes








            1 Answer
            1






            active

            oldest

            votes









            active

            oldest

            votes






            active

            oldest

            votes








            up vote
            4
            down vote



            accepted










            Use an old work box to house the splices



            There's a simple way out of this, and that's to use an old work box mounted into the ceiling drywall to house the electrical splices. A 3 gang switch box will do the trick, or you can use a 4 11/16" square box that's 1.5" or deeper if you can get an old work mountable version of that. (Really, anything that supplies more than 29.5 in3 of space will do.)






            share|improve this answer

























              up vote
              4
              down vote



              accepted










              Use an old work box to house the splices



              There's a simple way out of this, and that's to use an old work box mounted into the ceiling drywall to house the electrical splices. A 3 gang switch box will do the trick, or you can use a 4 11/16" square box that's 1.5" or deeper if you can get an old work mountable version of that. (Really, anything that supplies more than 29.5 in3 of space will do.)






              share|improve this answer























                up vote
                4
                down vote



                accepted







                up vote
                4
                down vote



                accepted






                Use an old work box to house the splices



                There's a simple way out of this, and that's to use an old work box mounted into the ceiling drywall to house the electrical splices. A 3 gang switch box will do the trick, or you can use a 4 11/16" square box that's 1.5" or deeper if you can get an old work mountable version of that. (Really, anything that supplies more than 29.5 in3 of space will do.)






                share|improve this answer












                Use an old work box to house the splices



                There's a simple way out of this, and that's to use an old work box mounted into the ceiling drywall to house the electrical splices. A 3 gang switch box will do the trick, or you can use a 4 11/16" square box that's 1.5" or deeper if you can get an old work mountable version of that. (Really, anything that supplies more than 29.5 in3 of space will do.)







                share|improve this answer












                share|improve this answer



                share|improve this answer










                answered Nov 19 at 12:45









                ThreePhaseEel

                29.3k104490




                29.3k104490






























                    draft saved

                    draft discarded




















































                    Thanks for contributing an answer to Home Improvement Stack Exchange!


                    • Please be sure to answer the question. Provide details and share your research!

                    But avoid



                    • Asking for help, clarification, or responding to other answers.

                    • Making statements based on opinion; back them up with references or personal experience.


                    To learn more, see our tips on writing great answers.





                    Some of your past answers have not been well-received, and you're in danger of being blocked from answering.


                    Please pay close attention to the following guidance:


                    • Please be sure to answer the question. Provide details and share your research!

                    But avoid



                    • Asking for help, clarification, or responding to other answers.

                    • Making statements based on opinion; back them up with references or personal experience.


                    To learn more, see our tips on writing great answers.




                    draft saved


                    draft discarded














                    StackExchange.ready(
                    function () {
                    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f150905%2fhow-to-organize-multiple-electrical-wires-going-into-an-ultra-thin-recessed-ligh%23new-answer', 'question_page');
                    }
                    );

                    Post as a guest















                    Required, but never shown





















































                    Required, but never shown














                    Required, but never shown












                    Required, but never shown







                    Required, but never shown

































                    Required, but never shown














                    Required, but never shown












                    Required, but never shown







                    Required, but never shown







                    Popular posts from this blog

                    Quarter-circle Tiles

                    build a pushdown automaton that recognizes the reverse language of a given pushdown automaton?

                    Mont Emei